Use
Fan coil units via ON/OFF or modulating control outputs:
Chilled / heated ceilings (or radiators) via ON/OFF or modulating control outputs:
Heat pumps with dx type equipment:
Functions
Setting of the control parameters (P01, etc., mentioned throughout the document) is described in section 4.15.
The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1), and maintains the setpoint by delivering actuator control commands to heating and/or cooling equipment. The following control outputs are available depending on the thermostat type:
The switching differential or proportional band is 2 K for heating mode and 1 K for cooling mode (adjustable via parameters P30 and P31).
The integral action time for modulating PI control is 5 minutes (adjustable via parameter P35).
The display shows the acquired room temperature or the Comfort setpoint, selecta- ble via parameter P06. The factory setting displays the current room temperature. Use parameter P04 to display the room temperature or setpoint in °F rather than °C as needed.
If the thermostat is used in a system with manual heating / cooling changeover (P01 = 2), the heating and cooling symbols on the display show the fan coil or terminal unit's status. Thus, the symbols are displayed even when the thermostat operates in the neutral zone. For all other cases, the heating and cooling symbols are displayed when the heating or cooling output is activated.
Concurrent display of the current temperature or setpoint in °C and °F (parameter P07) is possible on the thermostats without 7-day time program.