Instruction
Turn on / off : Press "On. / Off." to enable or disable the thermostat. Zoom in / decreased in numbers : Press the "Increase" or "Decrease" to set the desired temperature. Mode : Press "Mode" to switch the cooling or heating.
Fan speed : Press the "Fan"
to change the fan speed. (High, Med, Low, or Auto).
1. Temperature setting : Press "Increase" or "Decrease" to set the desired temperature. Press any other button to save the change or save automatically after 3 seconds.
2. Control valve : In cooling mode, if the room temperature is above the set temperature, the valve opens if the room temperature is below or equal to the set temperature, the valve closes in the heating mode if the room temperature is below the set temperature, the valve opens when the room temperature is above or smooth the set temperature, the valve closes.
3. Automatic control of the fan (Auto Fan speed Function): In cooling mode, if room temperature is above the set temperature by 3 ° C, the fan will switch on high (High) speed automatic; if the room temperature is above the set temperature by 2 ° C, the fan switch to the middle (Med) speed automatic; if the room temperature is below 1 ° C or equal to the set temperature, the fan switches to low (Low) speed automatic; In heating mode, if the room temperature is below the set temperature by 3 ° C, the fan will switch on high (High) speed automatic; if the room temperature is below the set temperature by 2 ° C, the fan switch to the middle (Med) speed automatic; if the room temperature is below 1 ° C or equal to the set temperature, the fan switches to low (Low) speed automatic;
4. Temperature Compensation (-9 ~ 9 ° C): When the thermostat is turned off, press the "Fan" and hold 3 sec., then increase or decrease the temperature and Harden pressing any other button or your changes are saved automatically after 3 seconds.
5. Sleep: When the thermostat is turned on, press the "Mode" and hold 3 sec., then increase or decrease the temperature and Harden pressing any other button or your changes are saved automatically after 3 seconds. In sleep mode, the fan operates in "Auto", click "Fan" or "mode" to turn off the "Auto".
In cooling mode, if the set temperature is lower than the temperature of sleep, the set temperature will increase by 1 ° C every half hour until compared with the temperature of sleep. Process is only possible in sleep mode.
In the heating mode, if the set temperature is higher than the temperature of sleep, the set temperature will decrease by 1 ° C every half hour until the match with a temperature of sleep. Process is only possible in sleep mode.
6. Frost protection : When the thermostat is turned off and the room temperature is below 5 ° C, mark appears on screen "Coupling" and "Heat", the valve opens automatically.
7. On. / Off. zapomenanie : To apron incl. / off in cases of power failure, press and hold for 3 seconds. "Large" when the thermostat is turned off.
8. Adjusting the contrast of the screen : When the thermostat is turned off, press and hold for 3 seconds. "Zoom Out". With the "Zoom" and "zoom" adjust the contrast. Harden change by pressing "Mode".
9. The backlight of the screen : When the thermostat is turned off, press and hold the "Up" and press when the screen is on, the backlight will be turned on always, if not included - will go out after 15 seconds.
10. Turn off the fan : When the thermostat is turned off, press and hold the "Mode" and press the "Zoom" and hold for about 5 seconds. If the screen is turned on, the fan does not turn off when the set temperature is reached, if not included - is turned off when the temperature reaches the set . Setting ID: When the thermostat is turned off, press and hold the "Fan" and click on "zoom" and hold for about 3 seconds. With the "Zoom" and "zoom in" Set ID, the value from 1 to 128.
Instructions network protocol :
Communication Protocol - Modbus (RS485).
ID - 1..128.
The data transfer rate - 9600, n, 8, 1.
You can read the status incl. / Off., temperature setting, mode, fan speed, temperature of the room, the cooling valve , the heating valve, change the status of the ban. You can write: status incl. / Off., Temperature setting, mode, fan speed, temperature of the room, change the status of the ban.
Values:
40001 ON / Off, on. - 00001, Off. - 00000.
40002, room temperature, 0 .. 50 ° C, then 31 ° C 31.
40003, temperature setting, 10 .. 30 ° C, then 10 ° C 10. 40004, mode, cooling - 00001, heating - 00002.
40005, fan speed, low - 00001, the average - 00002, high - 00003, stop - 00000, auto - 00004, 00005, 00006, 00007.
40006, the cooling valve is open - 00001, closed - 00000. 40007, the heating valve is opened - 00001, closed - 00000. 40008, ban variations ban - 00001, tolerance - 00000.
Technical data :
On Off.
The room temperature
Ustonovka temperature
Cooling Heating
Fan speed
Sleep mode
Prohibition of temperature change
1. Power supply: 220V ± 10% 50 / 60Hz
2. Control output: Repein ON / OFF
3. Functions: Coupling / Heating
4. Load: 3A / 250V
5. Wire size: ≤ 1.5 mm2
6. Operating temperature: 0 ~ 50 ° C
7. Basker temperature: -20 ° C ~ 60 ° C
8. Humidity: 10% ~ 90% (non-condensing) 9. Setting the temperature: 10 ~ 30 ° C
10. Accuracy: ± 1 ° C
11. The difference in temperature switch: 1 ° C