SIGA RCAS 6000/T/DX1

SIGA RCAS 6000/T/DX1

Product Code: SIGA RCAS 6000/T/DX1
Availability:
Pre-Order
Description

Equipment:

USED.
These recuperators, constituted of 10 series: DX1(internal),DX1/DP(external​), are used to regenerate heat in public rooms, like pub, meeting room, small and medium locals.
WORKING PRINCIPLES.
Inside hot air and outside cool air cross together but they don’t mix and mean while the hot of the inside defect ed air is being transferd to outside cool air. The efficiency of the recuperator in standard conditions (outside -5°C, inside 20°C with 50% of relative humidity) is always upper than 50%.
FEATURES.
Containment structure galvanized sheet steel, lined with acoustic insulation material exposed. Accommodated in n. 2 double inlet centrifugal fans which create the transmission air cross flow in exchange treated aluminium high-performance. Condense discharge drop tank,attack circular inlet and outlet Pleated filters efficiency G4 (standard) ,on request filtering cells F6 – F7 – F8 – F9 efficiency. Air-flow from 3000 to 20000 m /h, electric  motors UNEL MEC series IP55 protection ‘F’ class Volt 230/400/50 Hz IE2 EFFICIENCY.
ACCESSORIES.
Electronic digital speed controller singlephase with 5 speed positions.
Electric heater 
- Water heater
- Other accessories
- Electric control for CO2  filters

 

TECHNICAL GRAPHICS:

 

 

TECHNICAL CHARACTERISTICS:

 

 

RCAS3000

RCAS4000

RCAS5000

RCAS6000

RCAS7000

Power Options

B / F / Hz

380/3/50

380/3/50

380/3/50

380/3/50

380/3/50

Power consumption of the motor

kW

2x1,1

2x1,5

2x2,2

2x3

2x3

Operating current

A

2x2,7

2x3,5

2x4,9

2x6,6

2x6,6

The effectiveness of the heat exchanger winter (5C + 20C) / summer (34C + 26C)

%

60/52

54/48

54/48

53/47

54/48

Noise max / min

dB

71/67

71/67

71/67

71/67

71/69

Connection to the duct

mm

315

350

455

600

600

Dimensions horizontal H / W / D

mm

1300/600/1750

1300/850/1750

1300/850/1750

1600/1025/1950

1600x1025x1950

Weight

kg

178

185

220

360

360

 

 

RCAS8000

RCAS9000

Power Options

B / F / Hz

380/3/50

380/3/50

Power consumption of the motor

kW

2x4

2x4

Operating current

A

2x8,3

2x8,3

The effectiveness of the heat exchanger winter (5C + 20C) / summer (34C + 26C)

%

51/47

51/48

Noise max / min

dB

71/69

71/69

Connection to the duct

mm

600

600

Dimensions horizontal H / W / D

mm

1600/1025/1950

1750/1500/1960

Weight

kg

380

380

 

SIZE: 

Tags:
Tags: SIGA

Related Products

SIGA GROUP UAB © 2024