SIGA CSF-06-LI2TUBE3R

SIGA CSF-06-LI2TUBE3R

Product Code: SIGA CSF-06-LI2TUBE3R
Availability:
Pre-Order
Description

Description:

Ideally suited for use in air conditioning systems for hotels, offices, hospitals, schools and many more. The wide range of heating and cooling capacities, the efficient control of room conditions, and the independent user control offered by single room units are the major advantages available. With their unique characteristics and benefits, they are in a leading position in the market for environmental control. Their special feature's are quietness, cleanliness of filtered air and fresh air makeup either directly from outside or by a central air conditioning system. These benefits provide a guarantee of quality and product rationality in design, efficiency and use.

Finned coils Tubes are manufactured from 9,5 mm (3/8”). These have gas female connections (DN 1⁄2” size 02-03-04 DN 3⁄4”size 06-08) and incorpo- rate a drain and vent tapping. Available coils for 2-pipe installation 3R and for 4-pipe installations 2R+1 or 3R+1. Units are supplied as standard with pipe connections on the right when viewed from the front. The maximum working pressure is 24 bar and maximum water flow temperature 120°C.

Unit Casings manufactured in galvanized steel with external side RAL 9010 (pure white). The standard grille is manufactured from clear grey ABS plastic (RAL 7047).

Drain Trays galvanized sheet steel with an epoxy paint finish in both sides. On horizontal units the drain tray is fully insulated with 5 mm closed cell politeness foam, which has a class ‘1’ European std fire resistance. On vertical units, insulation only covers the area where condensate collects in the tray, which is inclined.
 

Fan Decks One or more centrifugal fans are fitted with galvanized scrolls and ABS impellers, which provide a spark free application. Size 02 and 03 utilise a mon- obloc group, statically and dynamically balanced. Fan decks can be easily removed for maintenance because mounted on slides and fixed only by two screws. Electric Motors PSC/AOM V230/1/50-60Hz permanently coupled capacitor. They have sealed for life sleeve bearings and a cast aluminium enclosure rated to IP42 with built in thermal overload protection. Insulation is to class ‘B’ 6-speeds are available (3-speed wired), of which three are usually wired to a fan speed switch.

Air Filters The synthetic media is cleanable efficiency is to class EU2-G2-M1.

Specifications:

Model CSF-хх-LI2TUBE3R

Mod.

02

03

04

06

08

Nominal Air Flow (40Pa) with std filter High

m3/h

370

505

700

995

1360

Nominal Air Flow (40Pa) with std filter Medium

m3/h

280

390

515

740

1110

Nominal Air Flow (40Pa) with std filter Low

m3/h

260

295

470

515

830

Cooling capacity

 

 

 

 

 

 

Total cooling capacity 7°C/12°C

W

2711

3967

5324

7396

10286

Sensible capacity

W

1773

2522

3428

4755

6569

Waterflow rate

l/h

465

681

914

1269

1765

Waterpressuredrops

kPa

18,7

47,6

32,4

29,6

39,8

Heating capacity

 

 

 

 

 

 

Heating capacity 50°C/40°C

W

3198

4483

6085

8581

11808

Waterpressuredrops

kPa

16,3

41,0

27,6

25,1

33,4

Heating capacity 70°C/60°C

W

5378

7471

10164

14334

19724

Waterflow rate

l/h

472

656

893

1259

1732

Waterpressuredrops

kPa

16,4

37,2

25,6

23,9

31,1

General data

 

 

 

 

 

 

Motor nominal power

W

20

20

45

45

3*25

Absorbed motor power

W

56

69

88

131

260

Absorbedmotorcurrent

A

0,21

0,31

0,38

0,57

1,15

Sound Power Levels (Lw)

dB(A)

49,2

53,2

51,2

56,1

58,6

Sound Pressure Levels (Lp)

dB(A)

40,2

44,2

42,2

47,1

49,6

Length of coil

mm

400

600

800

1000

1400

Coil Face area

m2

0,10

0,15

0,20

0,25

0,35

Coil Water content

l/h

0,90

1,38

1,83

2,28

3,18

Electric Heaters

W

700

1000

1500

2000

3000

High capacity electric heaters

W

1000

1200

2000

2500

4000

Size (Amm/232mm/425mm)

mm

740

940

1140

1340

1740

Weight

kg

16,7

19,8

23,9

29,3

45,2

SIGA GROUP UAB © 2024