SIGA CSHCFT-030

SIGA CSHCFT-030

Product Code: SIGA CSHCFT-030
Availability:
Pre-Order
Price: €0.00
Description

Description:

The range includes models that cover a refrigeration capacity ranging from 1 to 1500 kW. Compact chillers are for outdoor installation. The range has been designed for use both in the process and comfort sectors. The machines are equipped with all the components that ensure automatic cooling of water or a water/glycol solution. To guarantee maximum operating safety the units have (or can have) two completely independent refrigeration circuits. All units are supplied with a full oil and refrigerant load after having been factory tested. The chillers are divided in two product ranges: chillers with scroll compressors and chillers with screw compressors. For scrolls refrigerants used are R407C/R410A/R404A, while for screw compressors refrigerants are R407C/R134a/R404A. Models where scroll compressors are used are installed with shell and tube evaporators or plates evaporators (or coaxials). Models with screw compressors are installed with shell and tube evaporators, with optional opportunity of high efficiency evaporators for R134a refrigerant, which reach energetic Class A.

Options:

1.0 MECHANICAL CONFIGURATION

 

 

3.0 REFRIGERANT CIRCUIT CONFIGURATION (drawing code n. )

     

LNJ Low noise version (RV included)

 

HPG High pressure gauge

     

GPC Condenser coil protection

 

LPG Low pressure gauge

     

ATS Spring type antivibrant mounting

 

LT Low ambient temperature until -30°C (RV, RC,  EB included)

     

CV Epoxy coated condenser coil

 

LW Low water temperature until -10°C outlet (RC,  RV, thicker insulation included)

   

CF Condenser filter

 

PDS Desuperheater

   

CG Condenser treatment (blygold)

 

4.0 ELECTRIC CIRCUIT CONFIGURATION

         

2.0 HYDRIC CIRCUIT CONFIGURATION (drawing code n. )

 

 

OFC On-off compressors signal

   

T Tank carbon steelv included safety valve, air vent nipple (closed type)

 

OFR Remote control (on/off)

 

WP P3 Pump

 

OFRC Remote control display with on/off remote+alarm management, Carel microchiller2 (IP54)

DP Double P3 pump (valve betwwen tank and pump included)

 

RS485 Serial card for modbus RS485

 

PH P5 Pump

 

RV Electronic fan speed control

DPH Double P5 pump (valve betwwen tank and pump included)

 

RVG Volt-metric relay (CSF included)

BPA Automatic by pass until 50% of the flow rate

 

RC Cranckase heater

XV Expansion vessel kit available for closed-type tank

 

SF Soft start

RAGE Evaporator antifreeze heater

 

IRC Compressor inverter

RAGT Antifreeze heater inertial tank

 

EC EC fans

       

FL Flow switch installed

 

 

                 

LLA Electronic low level alarm

 

 

   

VTP Valve between tank and pump

 

                   

Technical Specification: 

Cooling CSHCFT

 

Model

030

038

045

055

061

070

NOMINAL COOLING CAPACITY (1)

 

kW

31,00

37,00

45,00

55,00

61,00

67,00

NOMINAL COOLING CAPACITY (1)

 

Frig/h

26660

31820

38700

47300

52460

57620

TOTAL COMPRESSORS NOMINAL ABSORBED POWER (1)

 

kW

8,40

11,50

12,40

17,30

16,40

19,30

COP

 

kW/kW

3,69

3,22

3,63

3,18

3,72

3,47

EER

 

kW/kW

3,15

2,82

3,25

2,91

3,01

2,89

ESEER

 

 

4,70

4,60

4,70

4,80

4,50

4,30

IPLV

 

 

5,30

5,20

5,30

5,50

5,00

4,80

COMPRESSORS

 

nr.

1,00

1,00

1,00

1,00

2,00

2,00

REFRIGERATING CIRCUITS

 

nr.

1,00

1,00

1,00

1,00

1,00

1,00

PARTITION STEP

 

nr.

1,00

1,00

1,00

1,00

1,00

1,00

REFRIGERANT

 

 

R410A

R410A

R410A

R410A

R410A

R410A

HYDRAULIC SECTION

 

 

 

 

 

 

 

 

NOMINAL WATER FLOW

 

m3/h

5,30

6,40

7,70

9,50

10,50

11,50

EVAPORATOR PRESSURE DROP

 

kPa

48,00

43,00

46,00

43,00

43,00

48,00

AVAILABLE PRESSURE (2)

 

mca

20,80

24,20

23,40

23,20

20,40

19,90

MAXIMUM PUMP ABSORBED POWER (2)

P3

kW

1,28

2,20

2,20

2,20

2,53

2,53

MAXIMUM PUMP ABSORBED CURRENT (2)

 

A

2,37

4,24

4,24

4,24

4,56

4,56

AVAILABLE PRESSURE (3)

 

mca

43,10

63,00

58,80

52,80

47,90

48,10

MAXIMUM PUMP ABSORBED POWER (3)

P5

kW

1,47

2,94

2,94

2,94

6,12

6,12

MAXIMUM PUMP ABSORBED CURRENT (3)

 

A

2,32

5,83

5,83

5,83

10,40

10,40

HYDRAULIC CONNECTIONS

 

BSP/DN

1 1/2"

1 1/2"

1 1/2"

1 1/2"

2"

2"

TANK VOLUME (4) - closed circuit configuration as per standard

 

dm3

200,00

200,00

200,00

200,00

390,00

390,00

FAN SECTION (AXIAL)

 

 

 

 

 

 

 

 

TOTAL AIR FLOW

 

m3/h

16000

16400

15000

15600

38000

36000

FANS

 

nr.

2,00

2,00

2,00

2,00

2,00

2,00

FANS ABSORBED POWER

 

kW

1,44

1,62

1,44

1,62

3,88

3,88

FANS ABSORBED CURRENT

 

A

2,82

3,08

2,82

3,08

7,80

7,80

TOTAL ELECTRIC DATA                                                                                                                                                                                                   

 

IP

IP54

IP54

IP54

IP54

IP54

IP54

NOMINAL ABSORBED POWER (5)

 

kW

9,80

13,10

13,80

18,90

20,30

23,20

MAXIMUM ABSORBED CURRENT(F.L.A.) (5)

 

A

22,10

27,60

32,80

39,50

46,30

51,50

MAXIMUM PEAK CURRENT  (L.R.A.) (5)

 

A

118,00

140,00

174,00

225,00

145,00

167,00

ELECTRIC FEED                                                                                                

 

 V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

NOISE DATA

 

 

 

 

 

 

 

 

SOUND PRESSURE (5) (6)

 

dB(A)

53,80

54,20

54,50

56,50

58,50

58,70

DIMENSIONS AND WEIGHT

 

 

 

 

 

 

 

 

LENGTH

 

mm

1610,00

1610,00

1610,00

1610,00

2220,00

2220,00

WIDTH

 

mm

860,00

860,00

860,00

860,00

1100,00

1100,00

HEIGHT

 

mm

1540,00

1540,00

1540,00

1540,00

2100,00

2100,00

WEIGHT EMPTY (5)

 

kg

290,00

300,00

330,00

365,00

595,00

605,00

WEIGHT OPERATIVE (5)

 

kg

300,00

310,00

340,00

375,00

610,00

620,00

 

Data referred to:

(1)  Inlet/Outlet  water temperature = +12/+7 °C - Condenser air temperature = +35°C; fouling factor = 0.000043 m²K/W

(2)  With option WP (P3 pump) or DP (double P3 pump)

(3)  With option PH (P5 pump) or DPH (double P5 pump)

(4)  With option T (Tank included safety valve, air vent nipple - closed configuration as per standard)

(5)  Data referred to standard configuration NT.NP (no tank - no pump)

(6)  Sound pressure level referred to measures according to normative ISO3744, pressure level at distance of 10 m, referred to free field on reflecting surface

(7) RV "fan speed cut-phase regulator" included

 

SIGA GROUP UAB © 2024