SIGA CSHECS-1330

SIGA CSHECS-1330

Product Code: SIGA CSHECS-1330
Availability:
Pre-Order
Description

Description:

The range includes models that cover a refrigeration capacity ranging from 1 to 1500 kW. Compact chillers are for outdoor installation. The range has been designed for use both in the process and comfort sectors. The machines are equipped with all the components that ensure automatic cooling of water or a water/glycol solution. To guarantee maximum operating safety the units have (or can have) two completely independent refrigeration circuits. All units are supplied with a full oil and refrigerant load after having been factory tested. The chillers are divided in two product ranges: chillers with scroll compressors and chillers with screw compressors. For scrolls refrigerants used are R407C/R410A/R404A, while for screw compressors refrigerants are R407C/R134a/R404A. Models where scroll compressors are used are installed with shell and tube evaporators or plates evaporators (or coaxials). Models with screw compressors are installed with shell and tube evaporators, with optional opportunity of high efficiency evaporators for R134a refrigerant, which reach energetic Class A.

Options:

1.0 MECHANICAL CONFIGURATION

   

3.0 REFRIGERANT CIRCUIT CONFIGURATION (drawing code n. )

           

LNJ Low noise version (RV included)

 

HPG High pressure gauge

     

GPC Condenser coil protection

 

LPG Low pressure gauge

     

ATS Spring type antivibrant mounting

 

PDS Partial heat recovery

     

CV Epoxy coated condenser coil

 

TDS Total heat recovery in parallel

               

CF Condenser filter

 

4.0 ELECTRIC CIRCUIT CONFIGURATION

   

CG Condenser treatment (blygold)

 

OFC On-off compressors signal

               

SLN Super low noise

   

OFR Remote control (on/off)

   

GPRC Metallic guards for refrigerant circuit

   

OFRC Remote control display with on/off remote+alarm management, Carel microchiller2 (IP54)

   
     

RS485 Serial card for modbus RS485

   

2.0 HYDRIC CIRCUIT CONFIGURATION (drawing code n. )

   

EC EC fans

   

T Tank in carbon steel including electronic low level alarm

   

LON LON board

   

WP P3 Pump including VTP

   

BAC Bacnet board

   

DP Double P3 pump (valve betwwen tank and pump included)

 

PLW Plant watch PRO

   

PH P5 Pump

 

PLV Plant visor

 

DPH Double P5 pump (valve betwwen tank and pump included)

 

SF Soft start

XV Expansion vessel kit available for closed-type tank

     

RAGE Evaporator antifreeze heater

   

RAGT Antifreeze heater inertial tank

   

 

Technical Specification: 

Cooling CSHECS

 

Model

1060

1200

1330

1430

NOMINAL COOLING CAPACITY (1)

 

kW

1048,00

1204,00

1328,00

1438,00

TOTAL COMPRESSORS NOMINAL ABSORBED POWER

 

kW

340,70

393,70

430,60

454,00

(1)

 

kW/kW

3,08

3,06

3,08

3,17

COP (1)

 

kW/kW

2,82

2,81

2,83

2,89

EER (1)

   

3,79

3,77

3,78

3,81

ESEER

   

4,32

4,30

4,31

4,35

IPLV

 

nr.

2,00

2,00

2,00

2,00

REFRIGERATING CIRCUITS

 

nr.

2,00

2,00

2,00

2,00

PARTITION STEP

 

nr.

0-25-50-75-100

0-25-50-75-100

0-25-50-75-100

0-25-50-75-100

REFRIGERANT

   

R407C

R407C

R407C

R407C

HYDRAULIC SECTION

           

NOMINAL WATER FLOW

 

m3/h

180,30

207,20

228,50

247,30

EVAPORATOR PRESSURE DROP

 

kPa

55,00

61,00

66,00

65,00

AVAILABLE PRESSURE (2)

 

mca

25,80

24,20

22,40

21,20

MAXIMUM PUMP ABSORBED POWER (2)

 

kW

23,50

23,50

23,50

23,50

MAXIMUM PUMP ABSORBED CURRENT (2)

 

A

39,00

39,00

39,00

39,00

HYDRAULIC CONNECTIONS

 

BSP/DN

200,00

200,00

200,00

200,00

TANK VOLUME (2)

 

dm3

800,00

800,00

1000,00

1000,00

FAN SECTION (AXIAL)

           

TOTAL AIR FLOW

 

m3/h

259200,00

291600,00

324000,00

356400,00

FANS

 

nr.

16,00

18,00

20,00

22,00

FANS ABSORBED POWER

 

kW

31,04

34,92

38,80

42,68

FANS ABSORBED CURRENT

 

A

62,40

70,20

78,00

85,80

TOTAL ELECTRIC DATA                                     

 

IP

IP54

IP54

IP54

IP54

MAXIMUM ABSORBED CURRENT(F.L.A.)

 

A

374,00

430,00

473,00

508,00

MAXIMUM PEAK CURRENT  (L.R.A.)

 

A

0,33

0,33

0,33

0,33

ELECTRIC FEED                                                  

 

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

NOISE DATA

           

SOUND PRESSURE (3)

 

dB(A)

71,70

72,00

72,30

72,70

DIMENSIONS AND WEIGHT

           

LENGTH

 

mm

8800,00

9750,00

10700,00

11650,00

WIDTH

 

mm

2210,00

2210,00

2210,00

2210,00

HEIGHT

 

mm

2450,00

2450,00

2450,00

2450,00

WEIGHT EMPTY

 

kg

7900,00

8620,00

9680,00

10610,00

WEIGHT OPERATIVE

 

kg

8250,00

8970,00

10060,00

11000,00

 

Data referred to:

           

(1) 100% of Load - Inlet/Outlet water temperature = +12/+7 °C - Condenser air temperature = +35°C; fouling factor = 0.000043 m²K/W.

   

(2) With options NT.WP (no tank - water pump) or T.WP (tank - water pump).

         

(3) Sound pressure level referred to measures according to normative ISO3744, pressure level at distance of 10 m, referred to free field on reflecting surface

 
             

 

SIGA GROUP UAB © 2024