SIGA CSHSBSF-470

SIGA CSHSBSF-470

Product Code: SIGA CSHSBSF-470
Availability:
Pre-Order
Price: €0.00
Description

Description:

The range includes models that cover a refrigeration capacity ranging from 1 to 1500 kW. Compact chillers are for outdoor installation. The range has been designed for use both in the process and comfort sectors. The machines are equipped with all the components that ensure automatic cooling of water or a water/glycol solution. To guarantee maximum operating safety the units have (or can have) two completely independent refrigeration circuits. All units are supplied with a full oil and refrigerant load after having been factory tested. The chillers are divided in two product ranges: chillers with scroll compressors and chillers with screw compressors. For scrolls refrigerants used are R407C/R410A/R404A, while for screw compressors refrigerants are R407C/R134a/R404A. Models where scroll compressors are used are installed with shell and tube evaporators or plates evaporators (or coaxials). Models with screw compressors are installed with shell and tube evaporators, with optional opportunity of high efficiency evaporators for R134a refrigerant, which reach energetic Class A.

Options:

1.0 MECHANICAL CONFIGURATION     3.0 REFRIGERANT CIRCUIT CONFIGURATION (drawing code n. )        
LNJ Low noise version (RV included)   HPG High pressure gauge      
GPC Condenser coil protection   LPG Low pressure gauge      
ATS Spring type antivibrant mounting   PDS Partial heat recovery with plate desuperheater      
CV Epoxy coated condenser coil   CSV Compressor valve    
CG Condenser treatment (blygold)   4.0 ELECTRIC CIRCUIT CONFIGURATION    
SLN Super low noise   OFC On-off compressors signal              
GPRC Metallic guards for refrigerant circuit     OFR Remote control (on/off)    
2.0 HYDRIC CIRCUIT CONFIGURATION (drawing code n. )     OFRC Remote control display with on/off remote+alarm management, Carel microchiller2 (IP54)    
T Tank in carbon steel including electronic low level alarm     RS485 Serial card for modbus RS485    
WP P3 Pump including VTP     EC EC fans    
DP Double P3 pump (valve betwwen tank and pump included)   LON LON board    
PH P5 Pump     BAC Bacnet board    
DPH Double P5 pump (valve betwwen tank and pump included)   PLW Plant watch PRO    
XV Expansion vessel kit available for closed-type tank   PLV Plant visor  
RAGE Evaporator antifreeze heater   SF Soft start
RAGT Antifreeze heater inertial tank      

 

Technical Specification: 

Cooling CSHSBSF Free Cooling

 

Model

430

470

500

540

610

NOMINAL COOLING CAPACITY (1)

 

kW

426,00

461,00

494,00

527,00

594,00

NOMINAL COOLING CAPACITY (1)

 

Frig/h

366365,00

396411,00

424518,00

453595,00

510779,00

TOTAL COMPRESSORS NOMINAL ABSORBED POWER (1)

 

kW

120,00

134,20

149,20

164,40

171,00

COP

 

kW/kW

3,55

3,43

3,31

3,21

3,47

EER

 

kW/kW

3,16

3,10

3,01

2,94

3,14

ESEER

   

4,40

4,30

4,20

4,10

4,30

IPLV

   

4,90

4,80

4,70

4,70

4,90

AIR TEMPERATURE 100% FREE COOLING (2)

 

С

0,30

-0,40

-1,10

-2,10

-0,70

COMPRESSORS

 

nr.

6,00

6,00

6,00

6,00

6,00

REFRIGERATING CIRCUITS

 

nr.

2,00

2,00

2,00

2,00

2,00

PARTITION STEP

 

nr.

4,00

4,00

4,00

4,00

4,00

REFRIGERANT

   

R410A

R410A

R410A

R410A

R410A

HYDRAULIC SECTION

             

NOMINAL WATER FLOW

 

m3/h

73,30

79,30

84,90

90,70

102,20

EVAPORATOR PRESSURE DROP (4)

 

kPa

82,00

80,00

81,00

83,00

79,00

FREE COOLING PRESSURE DROP (5)

 

kPa

151,00

160,00

169,00

149,00

164,00

AVAILABLE PRESSURE

 

mca

24,80

23,40

21,80

23,20

19,30

MAXIMUM PUMP ABSORBED POWER

P3

kW

16,22

16,22

16,22

16,22

19,94

MAXIMUM PUMP ABSORBED CURRENT

 

A

26,60

26,60

26,60

26,60

32,70

AVAILABLE PRESSURE

 

mca

52,60

51,20

49,80

50,80

43,10

MAXIMUM PUMP ABSORBED POWER

P5

kW

31,88

31,88

31,88

31,88

39,09

MAXIMUM PUMP ABSORBED CURRENT

 

A

53,50

53,50

53,50

53,50

65,60

HYDRAULIC CONNECTIONS

 

BSP/DN

DN150

DN150

DN150

DN150

DN150

TANK VOLUME (4)

 

dm3

500,00

500,00

500,00

500,00

500,00

FAN SECTION (AXIAL)

             

TOTAL AIR FLOW (6)

 

m3/h

144000,00

144000,00

144000,00

144000,00

180000,00

FANS

 

nr.

8,00

8,00

8,00

8,00

10,00

FANS ABSORBED POWER

 

kW

14,72

14,72

14,72

14,72

18,40

FANS ABSORBED CURRENT

 

A

30,64

30,64

30,64

30,64

38,30

TOTAL ELECTRIC DATA                 

 

IP

IP54

IP54

IP54

IP54

IP54

NOMINAL ABSORBED POWER (7)

 

kW

134,70

148,90

163,90

179,10

189,40

MAXIMUM ABSORBED CURRENT(F.L.A.) (7)

 

A

298,30

327,70

357,00

386,40

423,00

MAXIMUM PEAK CURRENT  (L.R.A.) (7)

 

A

525,70

578,40

607,70

637,10

757,30

ELECTRIC FEED                                        

 

V/Ph/Hz

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

NOISE DATA

             

SOUND PRESSURE (3)

 

dB(A)

68,50

68,50

68,60

68,60

70,00

DIMENSIONS AND WEIGHT

             

LENGTH

 

mm

5830,00

5830,00

5830,00

5830,00

7130,00

WIDTH

 

mm

2210,00

2210,00

2210,00

2210,00

2210,00

HEIGHT

 

mm

2450,00

2450,00

2450,00

2450,00

2450,00

WEIGHT EMPTY

 

kg

4150,00

4150,00

4150,00

4230,00

4900,00

WEIGHT OPERATIVE

 

kg

4450,00

4450,00

4450,00

4550,00

5250,00

 

Data referred to:

               
(1) Inlet/Outlet water temperature = +12/+7 °C - Condenser air temperature = +35°C; fouling factor = 0.000043 m²K/W      
(2) Inlet/outlet water temperature = +12/+7 °C            
(3) Sound pressure level referred to measures according to normative ISO3744, pressure level at distance of 10 m, referred to free field on reflecting surface
(4) Evaporator + valve + piping pressure drop (no free cooling)          
(5) Free cooling + evaporator + valve + one way valve + piping pressure drop          
(6) Minimum water content for the hydraulic circuit to be verified          
(7) Data referred to standard configuration (without pump)            
             

 

SIGA GROUP UAB © 2024