Description:
Produced in 8 sizes, air flow range from 2.500 to 20.000 m3/h. Those units are proper to realize heating and air conditioning installations for civil or industrial applica- tions on offices, hotels, hospitals, etc .. on large buildings they may be installed on each floor at a very actractive cost avoiding the high impact related to one main unit for a centralized installation. Working autonomously, efficient heat transfer for each unit permit to realize air conditioning installations with security, flexibility and exercise saving. Those units may be ducted to diffuse air in ambient or installed directly in the room with a plenum to diffuse the air. Very flexible units because can be installed both vertical or horizontal and allow all the possible configurations. As std supplied with double skin panels having 25 mm polyurethane foam internal insulation. Also available with direct expansion coil and with roof top for external installation. Between fan and coil it may be mounted germicide lamp which eliminate risk of contamination but also allow relevant energy saving by keeping aluminium fins perfectly clean and avoiding expensive and unuseful chemical treat- ment.
MotorV230-400/3/50Hz IP 55 Class ‘F’ - 1 speed – 4 Poles with adjustable belt and pulley
Coil Cu/Al - 24 Bar – Tmax120°C - geom. 25*22 mm - tubes 3/8” with manual air vent and drain FF – Standardc 10 FPI
Chassis Self supportingestrudedalu frames 30 mm thickness
Intake grill Painted single fixed blades
Filter Cleanable eff. 85% - class EU3-G3-M1 acrylic. On demand F7 panel filter
BacinellaEpoxy painted galvanized steel externally insulated with 5 mm polythene closed cells ‘1’ fire proof
Fan Centrifugal double inlet forwardly curved blades coupled to the motor with adjustable belt and pulley
Packing Plastic film protection
Inspection doors Totally dismountable fixed to the main frames with screwed knobs. Fan inspection door includes micro switch and net in accordance with safety standard
Panels Double skin 25 mmrockwool foam density 20 Kg/m3 external pre-coated galvanized RAL 9010 panel 0,8 mm thickness internal galvanized panel 0,6 mm thickness. (*) single skin version with galvanized steel 12/10 th. and internal insulation 10 mm polythene closed cells class ‘1’ fire proof
Specifications:
Model CSF-хх-TMH2TUBE6R |
Mod. |
25 |
40 |
60 |
80 |
105 |
130 |
160 |
200 |
Nominal Air Flow |
m3/h |
2 500 |
4 000 |
6 000 |
8 000 |
10 500 |
13 000 |
16 000 |
20 000 |
Cooling capacity |
|
|
|
|
|
|
|
|
|
Total cooling capacity 7°C/12°C |
kW |
19,41 |
31,01 |
47,23 |
62,85 |
81,74 |
104,00 |
127,19 |
159,83 |
Sensible capacity |
kW |
12,86 |
20,45 |
30,82 |
41,16 |
53,76 |
67,54 |
82,91 |
103,59 |
Waterflow rate |
l/h |
3331 |
5321 |
8103 |
10783 |
14026 |
17844 |
21823 |
27423 |
Heating capacity |
|
|
|
|
|
|
|
|
|
Heating capacity 70°C/60°C |
kW |
37,78 |
60,19 |
90,47 |
120,79 |
158,11 |
197,37 |
242,53 |
302,96 |
Waterflow rate |
l/h |
3318 |
5286 |
7946 |
10609 |
13887 |
17335 |
21301 |
26608 |
General data |
|
|
|
|
|
|
|
|
|
Motor nominal power |
kW |
0,55 |
1,1 |
1,5 |
3,0 |
4,0 |
5,5 |
5,5 |
7,5 |
Nominal absorbed motor current |
A |
1,5 |
2,8 |
3,7 |
6,9 |
8,7 |
11,6 |
11,6 |
15,3 |
Nominal RPM |
RPM |
1299 |
1023 |
754 |
1408 |
1238 |
1102 |
950 |
863 |
ESP available |
Pa |
223 |
232 |
234 |
230 |
233 |
224 |
225 |
230 |
Size (Amm) |
mm |
1150 |
1350 |
1650 |
1850 |
1950 |
2050 |
2150 |
2250 |
Size (Bmm) |
mm |
900 |
1050 |
1300 |
1550 |
1700 |
1900 |
2050 |
2250 |
Size (Cmm) |
mm |
600 |
700 |
850 |
1050 |
1100 |
1250 |
1300 |
1400 |
Weight |
kg |
|
|
|
|
|
|
|
|